Model No.: AIA-1

10KA 4pole 400v circuit breaker mcb for lighting or motor /components
 
<st

10KA 4pole 400v circuit breaker mcb for lighting or motor /components

 

Key Specification

10KA 4pole 400v circuit breaker mcb for lighting or motor /components supplier of CHINT

original metal components suppler of CHNT&Delixi

Key Parameters:

  • CE/CB/ISO9001/CCC certificates;
  • Rated voltage:single phase230/ 400VAC;
  • frequency:50/60Hz;
  • Rated current:50,63,80,100,125A;
  • 1/2/3/4poles optional;
  • Mechniacal life:20,0000times;
  • Electrical life 6,000times;
  • Flame-redardant:PA66 nylon material;
  • Protection degree:IP20;
  • Protections of short circuit&over load;
  • Standard:IEC60947-2;
  • Breaking Capacity:10/6KA;
  • Lighting/Motor protection optional;
  • more than 10 years orginal manufacturer;
  • product parts are manufactured by ourselves;
  • quality insurance 18months;

APPLICATION

high breaking miniature circuit breaker is used in lighting and motor protection system with protections of short circuit and over load. It mainly has the features of elegant and small, weight light, performance good and reliable, breaking capacity high, trip quickly, DIN installation and the material of shell and parts is high flameproof and anti-impact plastic ,life long. It is mainly applied in the system of 50/60Hz,single pole 230V,2,3,4poles for 400V as over load ,short circuit protection. And under voltage release, shunt release etc. And it also can be used in the isolation switch as the under voltage protection and remote distance breaking.

It conforms to IEC60947-2,GB14048.2

 

TECHNICAL PARAMETERS    

 

1) main type: C for lighting power distribution protection

 

    D for motive industry power distribution protection

 

2) rated current:32A,40A,50A,63A,80A,100A

 

3) poles:1,2,3,4pooles

 

4) DIN flushbonading installation

 

5) rated breaking capacity

 

Rated Current

(A)

Poles(P)

Rated Voltage

(V)

Rated Short Circuit Breaking Capacity

test expected current(A)

test power factor

32,40,50,

63,80,100

1

230/400

10000

0.45~0.50

2,3,4

230/400

10000

0.20~0.25

2,3,4

400

10000

0.45~0.50

 

6) power frequency voltage resistance: after humidity heat performance test, the circuit breaker can withstand 2500Vpower frequency voltage withstanding test for 1 minute ,but without insulation flashover and puncture

 

7) mechanical electrical life: mechanical life 20,000times,electrical life 6,000times

 

8) humidity heat withstanding:2category(temperature 55°C,relative humidity 95%).

 

9) wiring is terminal with clamp, cable dia.:50mm2below available for hard cable

bigPhoto
 Mr. John

Tel: 86-577-62053322
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

ZHEJIANG SINGI ELECTRICAL LLC [China (Mainland)]


Business Type:Manufacturer
City: Wenzhou
Province/State: Zhejiang
Country/Region: China (Mainland)

You May Like:

Product (196)